2.1
Ensure that ventilation systems are in good working order:
a. Check ACMV systems to ensure adequate ventilation in all occupied spaces, based on at least the minimum outdoor air supply rates specified in Singapore Standard SS553:2026 Code of Practice for Air-Conditioning and Mechanical Ventilation in Buildings3. Use of sensors and systems for monitoring outdoor air supply rate should be considered.
b. Check AHUs/FCUs/PAUs/FAFs/EAFs4 daily to ensure continuous operation, especially in occupied spaces.
c. Check all supply air diffusers and exhaust grilles to ensure airflow movement is in the correct direction.
d. Maintain ACMV systems regularly. This includes inspecting and cleaning supply fans and exhaust fans to ensure optimal operation, checking air ducts and dampers to ensure no air leakages or blockages, and checking filter seals to avoid air bypass. Recommended maintenance frequencies are specified in SS554:2026 Annex H. Replacement of filters should be done during non-operational periods, with the ACMV system turned off. Used filters should be properly disposed of in sealed bags. Maintenance staff should wear the appropriate PPE, comprising at least N95 masks, eye protection, and gloves, especially when replacing filters.
e. Check other systems to ensure there is no undesired air leakage into occupied spaces, including water seals in the sanitary system, cracks in pipes and ducts, and wall gaps. Rectify faults detected.
f. The air distribution system should be balanced to ensure outdoor air provision to all intended spaces.
2.2 Air-purging can rapidly remove pollutants from a space:
a. Consider air purging before each occupancy especially for spaces with high airborne disease transmission risk5 or when there is a need to rapidly remove pollutants
b. For buildings without air purging systems, consider extending operation of ACMV systems with outdoor air intake before each occupancy.
2.3 Air filters help to reduce indoor air pollution by trapping microscopic particles like dust, mold spores and other airborne pollutants:
a. Consider using efficient filters (at least MERV14, F8, or ePM1 70-80% is recommended) in AHUs to treat both outdoor and recirculated air. Alternatively, consider ensuring that the ACMV system is able to accommodate such filters when needed, e.g. during an epidemic or haze episode. Filters should be properly installed and maintained according to manufacturers’ recommendation.
2.4 Ventilation can help dilute the concentration of pollutants and airborne microorganisms and reduce transmission risk. For premises with limited ventilation and air filtration provision (e.g. meeting rooms with only FCU), consider below measures to increase ventilation:
a. Open operable windows and doors as frequently as possible, unless outdoor/outside air quality is poor. Air-conditioning should be reduced or turned off when doors and/or windows are opened to conserve energy..
b. Consider positioning fans to blow air out of windows to increase air exchange.
c. Add dedicated outdoor air supply and/or exhaust6
d. Where there is a high risk of airborne disease transmission5, localised air cleaning may be considered as an interim measure, in line with the recommendation for spaces without mechanical ventilation (please see sections 3.3 and 3.4).