| Air-conditioner (including single-phase Portable Air-Conditioner) | COP computed from results of VT > 0.9 x COP computed from Test Report data
|
| Refrigerator | Energy consumption computed from results of VT < 1.10 x Energy consumption computed from Test Report data |
| Clothes Dryer | Energy consumption computed from results of VT < 1.10 x Energy consumption computed from Test Report data
|
| Television | Energy consumption computed from results of VT < 1.10 x Energy consumption computed from Test Report data |
| Lamp | Refer to compliance conditions for lamps in Test Report section
|
| Water Heater | Energy consumption computed from results of VT < 1.10 x Energy consumption computed from Test Report data |
Three-Phase VRF Air-Conditioner
| COP computed from results of VT > 0.9 x COP computed from Test Report data (i.e. COP for 100%, 75%, 50% and 25% loading).
|
Three-Phase Induction Motor
| (a) For motors with rated output power of up to 150kW (100% - motor efficiency at rated output power) from results of VT ≤ 1.15 times of (100% - Minimum Efficiency at the rated output power for the respective IE classes)
(b) For motors with rated output power of above 150kW (100% - motor efficiency at rated output power) from results of VT ≤ 1.10 times of (100% - Minimum Efficiency at the rated output power for the respective IE classes)
|
| Commercial Storage Refrigerator | Energy consumption computed from results of VT < 1.10 x Energy Consumption computed from Test Report data |